List of parameters
Parameters
1-37
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Description: Displays supplementary control word.
Note: The following control bits are displayed in r0055:
Bit 00: r1198 Bit 0
Bit 01: r1198 Bit 1
Bit 02: r1198 Bit 2
Bit 03: r1198 Bit 3
Bit 04: r0837 Bit 0
Bit 05: r0837 Bit 1
Bit 08: r2349 Bit 0 (negated)
Bit 09: r1239 Bit 11
Bit 11: r1406 Bit 11
Bit 12: r1406 Bit 12
Bit 13: r2138 Bit 13 (negated)
Bit 15: r0836 Bit 1
Description: Displays the status word of the closed-loop control.
r0055.0...15 CO/BO: Supplementary control word / Suppl STW
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Fixed setpoint bit 0 Yes No -
01 Fixed setpoint bit 1 Yes No -
02 Fixed setpoint bit 2 Yes No -
03 Fixed setpoint bit 3 Yes No -
04 DDS selection bit 0 Yes No -
05 DDS selection bit 1 Yes No -
08 Technology controller enable Yes No -
09 DC braking enable Yes No -
11 Droop enable Yes No -
12 Torque control active Yes No -
13 External fault 1 (F07860) No Yes -
15 CDS bit 1 Yes No -
r0056.0...13 CO/BO: Status word, closed-loop control / ZSW cl-loop ctrl
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Initialization completed Yes No -
01 De-magnetizing completed Yes No -
02 Pulse enable present Yes No -
03 Soft starting present Yes No -
04 Magnetizing completed Yes No -
05 Voltage boost when starting Active Inactive 6300
06 Acceleration voltage Active Inactive 6300
07 Frequency negative Yes No -
08 Field weakening active Yes No -
09 Voltage limit active Yes No 6714
10 Slip limit active Yes No 6310