SINAMICS G120D List Manual (LH14), 01/2013
Description: Sets the smoothing time for the flux setpoint.
Description: Displays the smoothed flux setpoint.
The value is referred to the rated motor flux.
Description: Sets the smoothing time for the flux setpoint in the field-weakening range
Note: Only the flux setpoint rise is smoothed
Description: Displays the pre-control value for the field weakening current.
Description: Display and connector output for the output of the field weakening controller (synchronous motor).
Index: [0] = PI output
[1] = I output
p1582[0...n] Flux setpoint smoothing time / Flux setp T_smth
Access level: 3 Calculated: p0340 = 1,3 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 6722, 6724
Min Max Factory setting
4 [ms] 5000 [ms] 15 [ms]
r1583 Flux setpoint smoothed / Flux setp smooth
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dyn. index: -
Units group: - Unit selection: - Func. diagram: 6722, 6723, 6724
Min Max Factory setting
- [%] - [%] - [%]
p1584[0...n] Field weakening operation flux setpoint smoothing time / Field weak T_smth
Access level: 4 Calculated: p0340 = 1,3 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 6722
Min Max Factory setting
0 [ms] 20000 [ms] 0 [ms]
r1589 Field-weakening current pre-control value / I_FieldWeak prectr
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2002 Dyn. index: -
Units group: 6_2 Unit selection: p0505 Func. diagram: 6724
Min Max Factory setting
- [Arms] - [Arms] - [Arms]
r1593[0...1] CO: Field weakening controller / flux controller output / Field/Fl_ctrl outp
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2002 Dyn. index: -
Units group: 6_2 Unit selection: p0505 Func. diagram: 6724
Min Max Factory setting
- [Arms] - [Arms] - [Arms]