Parameters
List of parameters
1-316
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Dependency: The parameterized fault response is only effective if the technology controller mode is set to p2251 = 0 (technology
controller as main setpoint).
Refer to: p2267, p2268, r2344
Refer to: F07426
Notice: Dependent upon the application, the changing over of the setpoint when fault F07426 occurs can lead to the fault
condition disappearing and the re-activation of the technology controller. This can repeat itself and cause limit oscil-
lations. In this case, a different fault response or a different fixed setpoint 15 for the fault response p2345 = 2 should
be selected.
Note: The parameterized fault response can only be achieved if the default fault response of the technology controller
fault F07426 is set to "NONE" (see p2100, p2101). If a fault response other than "NONE" is entered in p2101 for
F07426, p2345 must be set to zero.
If the fault occurs during ramping up to the starting setpoint p2302, this starting setpoint is retained as the final value
(there is no changeover to the fault response setpoint).
Description: Displays the status word of the technology controller.
Description: Sets the assigned encoder.
The actual value preprocessing and the closed-loop position control are carried out using the assigned encoder.
Value: 0: No encoder
1: Encoder 1
2: Encoder 2
Dependency: Refer to: p0187, p0188
r2349.0...12 CO/BO: Technology controller status word / Tec_ctrl status
CU240D-2_DP
CU240D-2_DP_F
CU240D-2_PN
CU240D-2_PN_F
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7958
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Technology controller de-activated Yes No -
01 Technology controller limited Yes No -
02 Technology controller motorized potentiom-
eter limited max.
Yes No -
03 Technology controller motorized potentiom-
eter limited min.
Yes No -
04 Technology controller speed setpoint total in
setpoint channel
Yes No -
05 Technology controller RFG bypassed in the
setpoint channel
Yes No -
06 Technology controller starting value at the
current limit
No Yes -
08 Technology controller actual value at the
minimum
Yes No -
09 Technology controller actual value at the
maximum
Yes No -
10 Technology controller output at the mini-
mum
Yes No -
11 Technology controller output at the maxi-
mum
Yes No -
12 Fault response active Yes No -
p2502[0...n] LR encoder assignment / Encoder assignment
CU250D-2_DP_F
CU250D-2_PN_F
Access level: 1 Calculated: - Data type: Integer16
Can be changed: C(25) Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 4010
Min Max Factory setting
0 2 1