List of parameters
Parameters
1-193
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Note: The controller settings are also used in the current controller of the DC braking (refer to p1232).
For p1346 = 0, the following applies:
The integral time of the I_max voltage controller is de-activated.
Description: Displays the economic factor determined for optimizing motor consumption.
Dependency: Refer to: p1335
Note: The value is only determined for operating modes with Economic (p1300 = 4, 7).
Description: Sets the maximum output frequency for resonance damping for U/f control.
Resonance damping is inactive above this output frequency.
Dependency: Refer to: p1338, p1339
Note: For p1349 = 0, the changeover limit is automatically set to 95 % of the rated motor frequency - however, to a max.
of 45 Hz.
Description: Sets whether the voltage is continuously increased during the magnetizing phase (p1350 = 1, On) or whether it
jumps directly to the voltage boost (p1350 = 0, Off).
Value: 0: OFF
1: ON
Note: The settings for this parameter have the following advantages and disadvantages:
0 = off (jump directly to voltage boost)
Advantage: Flux is established quickly -> torque is quickly available
Disadvantage: The motor can move while it is being magnetized
1 = on (voltage is continually established)
Advantage: The motor is unlikely to rotate
Disadvantage: The flux is established slower -> torque is available later
Description: Sets the frequency setting value at the slip compensation output for starting up with motor holding brake.
r1348 CO: U/f control Eco factor actual value / U/f Eco fac act v
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dyn. index: -
Units group: - Unit selection: - Func. diagram: 6300
Min Max Factory setting
- [%] - [%] - [%]
p1349[0...n] U/f mode resonance damping maximum frequency / Uf res_damp f_max
Access level: 3 Calculated: p0340 = 1 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 6310
Min Max Factory setting
0.00 [Hz] 3000.00 [Hz] 0.00 [Hz]
p1350[0...n] Soft starting / Soft starting
Access level: 3 Calculated: - Data type: Integer16
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 1690
Min Max Factory setting
0 1 0
p1351[0...n] CO: Motor holding brake starting frequency / Brake f_start
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 6310
Min Max Factory setting
-300.00 [%] 300.00 [%] 0.00 [%]