Parameters
List of parameters
1-382
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
725: Wait for cyclic
740: Check the ability to operate
745: Start cyclic calculations
750: Interrupt enable
800: Initialization finished
Index: [0] = System
[1] = Partial boot
Description: Displays whether writing to parameters is inhibited.
r3996[0] = 0:
Parameter write not inhibited.
0 < r3996[0] < 100:
Parameter write inhibited. The value shows how the calculations are progressing.
Index: [0] = Progress calculations
[1] = Cause
Note: Re index 1:
Only for internal Siemens troubleshooting.
Description: Displays the encoder diagnostics for the PROFIdrive interface.
Description: Sets the mode to reset the actual value in XIST_ERW (CO: r4653).
Value: 0: Inactive
1: Reset with zero mark
2: Reset with BICO
3: Reset with selected zero mark
Index: [0] = Encoder 1
[1] = Encoder 2
[2] = Encoder 3
Dependency: Refer to: r4653, r4654, p4655
Note: If value = 1:
The value in XIST1_ERW is reset when passing every zero mark.
If value = 2:
The value in XIST1_ERW is reset with a 0/1 edge via binector input p4655.
If value = 3:
The value in XIST1_ERW is reset after a 0/1 edge via binector input p4655 when passing the next zero mark.
r3996[0...1] Parameter write inhibit status / Par_write inhib st
Access level: 3 Calculated: - Data type: Unsigned8
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
r4640[0...95] Encoder diagnostics state machine / Enc diag stat_ma
Access level: 4 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
p4652[0...2] XIST1_ERW reset mode / XIST1_ERW res mode
Access level: 3 Calculated: - Data type: Integer16
Can be changed: C(3) Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 4750
Min Max Factory setting
0 3 0