EasyManua.ls Logo

Siemens SINAMICS G120D - r0481[0...2] CO: Encoder status word Gn_ZSW; Enc Gn_ZSW; r0482[0...2] CO: Encoder actual position value Gn_XIST1; Enc Gn_XIST1

Siemens SINAMICS G120D
910 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of parameters
Parameters
1-89
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Description: Displays the encoder status word Gn_ZSW according to PROFIdrive.
Index: [0] = Encoder 1
[1] = Encoder 2
[2] = Encoder 3
Notice: Information on Gn_STW/Gn_ZSW can, e.g. be found in the following literature:
SINAMICS S120 Function Manual Drive Functions
Note: Re bit 14:
Displays the acknowledgement for "activate parking encoder" (Gn_STW.14 = 1) or encoder position actual value
(Gn_XIST1) invalid.
Re bit 14, 15:
r0481.14 = 1 and r0481.15 = 0 can have one of the following causes:
- the encoder is parked.
- the encoder is de-activated.
- the encoder is being commissioned.
- no parameterized encoder available.
- encoder data set is being changed over.
r0481.14 = 1 and r0481.15 = 1 has the following significance:
An encoder error has occurred and the encoder position actual value (Gn_XIST1) is invalid.
Description: Displays the encoder actual position value Gn_XIST1 according to PROFIdrive.
Index: [0] = Encoder 1
[1] = Encoder 2
[2] = Encoder 3
Note: - this value is reset if necessary when the "parking encoder" (r0481.14) function is de-selected.
- in this value, the measuring gear (p0432, p0433) is only taken into account when the position tracking is activated
(p0411.0 = 1).
r0481[0...2] CO: Encoder status word Gn_ZSW / Enc Gn_ZSW
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 4010, 4704, 4730,
4750
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Function 1 active Yes No -
01 Function 2 active Yes No -
02 Function 3 active Yes No -
03 Function 4 active Yes No -
04 Value 1 Displayed in r0483 Not present -
05 Value 2 Displayed in r0483 Not present -
06 Value 3 Displayed in r0483 Not present -
07 Value 4 Displayed in r0483 Not present -
08 Measuring probe 1 deflected Yes No -
09 Measuring probe 2 deflected Yes No -
11 Encoder fault acknowledge active Yes No 9676
13 Absolute value cyclically Displayed in r0483 No -
14 Parking encoder active Yes No -
15 Encoder fault Displayed in r0483 None -
r0482[0...2] CO: Encoder actual position value Gn_XIST1 / Enc Gn_XIST1
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 1580, 1680, 4704,
4735, 4740, 4750
Min Max Factory setting
- - -

Table of Contents