List of parameters
Parameters
1-461
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Description: Sets the signal sources for F-DO 0 (X131.6).
The 6 signal sources in p10142[0...5] are AND'ed and the result is output at F-DO 0.
Value: 0: No function
1: STO active
2: SS1 active
5: SLS active
6: SSM feedback signal active
7: Safe state
9: Internal event
12: SDI positive active
13: SDI negative active
Index: [0] = AND logic operation input 1
[1] = AND logic operation input 2
[2] = AND logic operation input 3
[3] = AND logic operation input 4
[4] = AND logic operation input 5
[5] = AND logic operation input 6
Note: F-DO: Failsafe Digital Output
Description: Sets the test of the feedback line for forced checking procedure.
Note: F-DO: Failsafe Digital Output
Description: Sets the test stop mode for the safety digital output (F-DO)
Value: 2: Test mode 2 read back F-DO in DI (relay circuit)
3: Test mode 3 read back F-DO in DI (actuator with feedback signal)
4: Test mode 4 evaluation of two internal diagnostic signals
Dependency: Refer to: p10001, p10003, p10007, p10046
04 SLS_active Selected Not selected -
05 SDI_pos_active Selected Not selected -
06 SDI_neg_active Selected Not selected -
p10142[0...5] SI F-DO 0 signal sources (processor 2) / SI F-DO 0 S_src P2
CU240D-2_DP_F
CU240D-2_PN_F
CU250D-2_DP_F
CU250D-2_PN_F
Access level: 3 Calculated: - Data type: Integer16
Can be changed: C(95) Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 2857
Min Max Factory setting
0 13 0
p10146 SI test sensor feedback signal / SI test sens FS
CU240D-2_DP_F
CU240D-2_PN_F
CU250D-2_DP_F
CU250D-2_PN_F
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: C(95) Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 2848
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Test F-DO 0 Test active No test -
p10147 SI F-DO test stop mode / SI F-DO test mode
CU240D-2_DP_F
CU240D-2_PN_F
CU250D-2_DP_F
CU250D-2_PN_F
Access level: 3 Calculated: - Data type: Integer16
Can be changed: C(95) Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
2 4 4