Maintenance Object Repair Procedures
555-233-123
10-718 Issue 4 May 2002
Inter-Duplication Interface Circuit Pack Loop
Back Test (#280)
This test loops back data through the UART used to communicate with the other
Duplication Interface circuit pack. The data is generated by the Duplication
Interface circuit pack processor and is looped through the UART. The test is done
entirely on the Duplication Interface circuit pack. The test passes if the data sent
matches the data received. This test does not check the physical serial channel
that is printed on the backplane or carried by the ICC.
Table 10-268. TEST #280 Inter-Duplication Interface Circuit Pack Loop Back Test
Error
Code
Te s t
Result Description/Recommendation
1000 ABORT System resources required to run this test are not available.
2000 ABORT Response to the test request was not received within the
allowable time period.
2033 ABORT Internal system error
1. Retry the command at 1-minute intervals a maximum of 5
times.
FAIL The tested UART on the Duplication Interface circuit pack is
defective.
1. Replace the Duplication Interface circuit pack.
2. Rerun the test.
NO
BOARD
The Duplication Interface circuit pack B has failed to reply to
handshaking either from Duplication Interface circuit pack A.
1. Refer to NO BOARD description for the Duplication
Interface Circuit Pack Status Query Test (#315).
PASS The Inter-DUPINT UART on the tested Duplication Interface
circuit pack is good.
Continued on next page