Maintenance Object Repair Procedures
555-233-123
10-332 Issue 4 May 2002
Table 10-129. TEST #122 Cabinet Temperature Query Test
[Non-Variable Speed Fans]
Error
Code
Te s t
Result Description/Recommendation
1000 ABORT System resources required to run this test are not available.
1. Retry the command at 1-minute intervals a maximum of 5
times.
2000 ABORT Response to the test request was not received within the
allowable time period.
1. Retry the command at 1-minute intervals a maximum of 5
times.
2. If the test continues to ABORT with Error Code 2000,
check for system powering problems with the A carrier
(PPN or EPN). Look for and resolve all AC-POWER and
CARR-POW alarms in a multicarrier cabinet system or
DC-POWER alarms in a single-carrier cabinet system.
Then, repeat the test.
3. If the test continues to ABORT with a Error Code 2000,
check for and resolve all DUPINT (Duplication Interface)
errors in a Duplicated Option PPN, PR-MAINT
(Maintenance/Tape Processor) errors in a standard PPN,
or MAINT (EPN Maintenance circuit pack) errors in an
EPN. Then, repeat the test.
4. If the test continues to ABORT with a Error Code 2000,
escalate the problem.
2029 ABORT Internal System Error.
1. Retry the command at 1-minute intervals a maximum of 5
times.
Continued on next page