DID-DS1 (DS1 DID Trunk)
Issue 4 May 2002
10-531 555-233-123
FAIL Test failed due to Internal System Error.
1. Retry the command at 1-minute intervals a maximum of 5
times.
PASS Trunk translation has been updated successfully. The current
trunk states kept in the DS1 Interface circuit pack and switch
software are consistent. If the trunk is busied out, the test does
not run, but returns PASS. To verify that the trunk is in-service:
1. Enter status-command to verify that the trunk is
in-service. If the trunk is in-service, no further action is
necessary. If the trunk is out-of-service, continue to Step
2.
2. Enter release-trunk command to put trunk back into
in-service.
3. Retry the test command.
0NO
BOARD
The test could not relate the internal ID to the port (no board).
This could be due to incorrect translations, no board is
inserted, an incorrect board is inserted, or an insane board is
inserted.
1. Check to ensure that the board translations are correct.
Use the list config command, and resolve any problems
that are found.
2. If the board was found to be correctly inserted in step 1,
issue the busyout board command.
3. Issue the reset board command.
4. Issue the release busy board command.
5. Issue the test board long command. This should
re-establish the linkage between the internal ID and the
port. If this is not the case, check to see that there is a
valid board inserted.
Table 10-195. TEST #36 Port Audit and Update Test Continued
Error
Code
Te s t
Result Description/Recommendation
Continued on next page