Maintenance Object Repair Procedures
555-233-123
10-598 Issue 4 May 2002
Hardware Error Log Entries and Test to Clear
Val ues
Notes:
a. These are in-line errors that have no specific test associated with them.
Refer to the following table for an explanation and appropriate action.
b. This is a software audit error that does not indicate any hardware
malfunction. Run the Short Test Sequence and investigate associated
errors (if any).
c. Aux data 57376 - No loop current on incoming call
Aux data 57424 - No loop current on outgoing call
Table 10-222. DIOD Trunk Error Log Entries
Error Type
Aux
Data Associated Test
Alarm
Level
On/Off
Board Test to Clear Value
0
1
1 Run the Short Test Sequence first. If all tests pass, run the Long Test Sequence. Refer to the
appropriate test description and follow the recommended procedures.
0 Any Any Any test port PCSSpp sh r 1
15 (b) any Port Audit Update
Test (#36)
18 0 busyout trunk
<grp>/<mbr>
769 (a) 57392 None MAJ/MIN/
WRN
2
2 Minor alarms on this MO may be downgraded to warning alarms based on the values used in the set
options command. If the Minor alarm is not downgraded by the set-options values, the Minor alarm
is upgraded to a Major alarm if 75 percent of the trunks in this trunk group are alarmed.
ON
1537 Dial Tone Test (#0) MAJ/MIN/
WRN
2
ON test port PCSS l r 2
1793 Loop Around and
Conference Test
(#33)
MAJ/MIN/
WRN
2
ON test port PCSS l r 3
2049 NPE Cross Talk
Test (#6)
MAJ/MIN/
WRN
2
ON test port PCSS l r 3
2561 (a, d) 57345 None
2817 (a,e) 57393 None
3073 (a,c) 57376 None
3073 (a,c) 57424 None
3585 (a,c) 57424 None
Continued on next page