Maintenance Object Repair Procedures
555-233-123
10-1342 Issue 4 May 2002
2000 ABORT Response to the test request was not received within the allowable
time period.
1. Retry the command at one-minute intervals a maximum of 5
times.
2. If the test continues to ABORT with Error Code 2000, check
for system powering problems with the A carrier (PPN or
EPN). Look for and resolve all AC-POWER and CARR-POW
alarms in a multicarrier cabinet system or DC-POWER alarms
in a single-carrier cabinet system. Repeat the test.
3. If the test continues to ABORT with a 2000 error code, check
for and resolve all DUPINT (Duplication Interface) errors in a
Duplicated Option PPN, PR-MAINT (Maintenance/Tape
Processor) errors in a standard PPN, or MAINT (EPN
Maintenance circuit pack) errors in an EPN. Repeat the test.
4. If the test continues to ABORT with a 2000 error code,
escalate the problem.
2028 ABORT Internal System Error prevented the extinguishing of the Battery
Charger status LED.
1. Retry the command at one-minute intervals a maximum of 5
times.
2029 ABORT Internal System Error.
1. Retry the command at one-minute intervals a maximum of 5
times.
Table 10-495. TEST #5 Battery & Battery Charger Query Test Continued
Error
Code
Tes t
Result Description/Recommendation
Continued on next page