POWER (Battery & Battery Charger for DC-Powered
Systems
Issue 4 May 2002
10-1351555-233-123
2029 ABORT Internal system error
1. Retry the command at 1-minute intervals a maximum of 5
times.
any FAIL The Duplication Interface circuit pack in a PPN for a high or
critical reliability system is incorrectly reporting a problem with
power. If this test fails, the problem is with the circuit pack and
not with POWER.
1. The suspect circuit pack, depending on the system
configuration, should be replaced and the test rerun.
PASS All that can be inferred is that the DUPINT (Duplication
Interface) circuit pack in a PPN for a high or critical reliability
system is working properly.
Table 10-497. TEST #5 Battery & Battery Charger Query Test — Continued
Error
Code
Te s t
Result Description/Recommendation
Continued on next page