test environment
Issue 4 May 2002
8-437555-233-123
Feature Interactions
The long test recycles power in some specified cabinet on non-SPE and
maintenance board carriers and is destructive. Specifically, the “a” carrier of PPNs
and EPNs does not have power recycled. In PPNs containing duplicated SPEs
the “b” carrier also does not have power recycled. All port carriers are recycled,
and service is interrupted for each port carrier. If a carrier containing an active EI
is recycled, communication with that cabinet is disrupted. If a carrier containing an
active tone-clock board is recycled, all ports in the cabinet or port network are
service disrupted.
Action/Object Qualifier Qualifier Description Logins Defaults
Feature
Interactions
test environment location
short
long
repeat
number
clear
schedule
Cabinet (1-3); 1 = PPN, 2-3 =
optional EPN.
Option for a brief series of
nondestructive diagnostic tests.
Option for a longer, more
comprehensive series of both
destructive and nondestructive
diagnostic tests.
How many times each test in the
sequence is repeated (1-100)
This option causes the test sequence
(short or long) to repeat until the
alarm (if any) is cleared or a single
test in the sequence fails.
1
Command is validated and then a
scheduling form displays to schedule
execution of the command. The
command is then placed in the
command queue and is executed at
the specified time. The information
displayed by the command is sent to
the system printer instead of the
screen.
2
Examples:
test environment
test environment schedule
test environment 1 sh
test environment 1 l r 25
test environment 01 l r 25
test environment 01 l r 25
schedule
test environment 2 l c
test environment 3 c
1 If no alarms are registered against the maintenance object then the test sequence is run only once. The long clear
option forces a clear of all alarms if no errors are encountered during testing. The short clear option only clears
alarms pertinent to tests in the short sequence.
2 Refer to the Report Scheduler and System Printer feature specification for more details.
init
inads
craft
Cabinet = 1;
test sequence =
short; repeat = 1
See below