Variables and Commands CDHD
226 VarCom Reference Manual
MFOLDR
Definition Motor Foldback Recovery Time
Type Variable (R)
Description Gets/sets the recovery time for motor foldback.
After the drive enters the motor foldback state (MFOLD=1),
and the current folds back to MICONT, this is the minimum
amount of time that the current must be held at 0 before it
can be MIPEAK for the full MFOLDD time.
Syntax Read: MFOLDR
Write: MFOLDR <value>
Firmware 1.0.6
Drive status Disabled
Range Not Applicable
Default value 70.000
Unit second
Non-volatile No
See also MFOLDD
MFOLDDIS
MFOLDT
MICONT
MIPEAK
CANopen 2031h, sub-index 0