CDHD Variables and Commands
VarCom Reference Manual 351
RESAMPLRANGE
Definition Resolver Amplitude Range
Type Variable (R/W)
Description Gets/sets the acceptable range of resolver sine/cosine
signals, expressed as a percentage, around their nominal
value.
The default value of 10% means the sine/cosine signals are
allowed to deviate up to 10% from the nominal before an
Out-Of-Range Fault is declared.
Syntax Read: RESAMPLRANGE
Write: RESAMPLRANGE <value>
Firmware 1.0.6
Drive status Enabled | Disabled
Range 0 to 100
Default value 10
Unit %
Non-volatile Yes
See also FEEDBACKTYPE
RESBW
SININIT
SINPARAM
CANopen 20BBh, sub-index 0