5.6 Gland plate for connecting cables, converter with IP55 degree of
protection
5.6.1 Mount the gland plate for connecting cables
Requirement
To mount the gland plate, you will need this torx screwdriver:
T20 for frame sizes FSA…FSC
T25 from frame size FSD1
Procedure
To install the gland plate, proceed as follows:
1. Undo the screws of the plate, which is mounted on the underside of the converter (as
delivered).
Figure5-8 Converter in the basic version
2. Screw the gland plate for the connecting cables in place with the following torque:
Frame size FSA ... FSC: 2Nm
From frame size FSD1: 5Nm
Figure5-9 Converter with gland plate