17.3.2 380 V … 415 V 3 AC / 440 V … 500 V 3 AC
Technical data
The rated converter power is the mechanical shaft power of a typical 8-pole induction motor,
which can be operated at the converter at its rated operating point without overloading the
converter.
Table 17-9 Power and currents
Property Unit Article number: 6SL4113-...□□-..F0
08 10 11 12 13 15 16
Rated power at 400V
With low
overload
kW 1.1 1.5 2.2 3.0 4.0 5.5 7.5
With high
overload
kW 0.75 1.1 1.5 2.2 3.0 4.0 5.5
Rated power at 480 V With low
overload
hp 1.5 2.0 3.0 4.0 5.0 7.5 10.0
With high
overload
hp 1.0 1.50 2.0 3.0 4.0 5.0 7.5
Input current at line voltage
3 AC380V…415V
With low
overload
A 3.3 4.1 5.6 7.3 9.6 12.9 17.3
With high
overload
A 2.6 3.7 4.4 6.2 8.1 10.7 14.6
Output current at line voltage
3 AC380V…415V
Without
overload
A 4.1 4.9 6.7 8.8 11.3 14.9 19.5
With low
overload
A 3.9 4.7 6.5 8.5 11.0 14.5 19.0
With high
overload
A 2.9 3.9 4.7 6.5 8.5 11.0 14.5
Input current at line voltage
3 AC440V…500V
With low
overload
A 3.0 3.7 4.9 6.1 7.3 11.0 14.0
With high
overload
A 2.4 3.6 3.8 5.3 6.6 8.4 12.1
Output current at line voltage
3 AC440V…500V
Without
overload
A 3.1 3.5 5.0 6.4 7.8 11.3 14.4
With low
overload
A 3.0 3.4 4.8 6.2 7.6 11.0 14.0
With high
overload
A 2.1 3.0 3.4 4.8 6.2 7.6 11.0
Output current for synchronous re‐
luctance motors for line voltage 3
AC400V
A 3.9 4.7 6.5 8.5 11.0 14.5 19.0
Technical data
17.3Power, input current, output current
SINAMICS G220 converter
804 Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB