Table 14-26 Parameter access via DS47
Register Description Access
1)
Unit Scaling Value range Data / parameter
40601 DS47 Control R/W - - - -
40602 DS47 header R/W - - - -
40603 DS47 data 1 R/W - - - -
…
40722 DS47 data 120 R/W - - - -
1)
"R" stands for read (with FC03), "W" for write (with FC06 or FC16) and "R/W" for read/write
14.5.3 Application data unit
Overview
The controller communicates with the converter via the application data unit.
Description of function
5SBOTBDUJPO*%1SPUPDPM*%
-FOHUI
6OJU*%
'$PEF
#ZUF#ZUF#ZUFT#ZUFT#ZUFT
#ZUFT
3URWRFRO'DWD8QLW3'8
.PECVT"QQMJDBUJPO)FBEFS
"QQMJDBUJPO%BUB6OJU"%6
%BUB
Figure14-30 Design of the application data unit
The application data unit (ADU) comprises the following elements:
• The Modbus application header is a 7-byte header.
The "Unit ID" byte has no signicance for Modbus TCP.
• The protocol data unit (PDU) comprises the following components:
– The function code (FCode) indicates whether the controller is writing data to the
converter or reading data from the converter.
– The data (Data) depends on the FCode and can contain information such as the registers
or parameter numbers and parameter values.
14.5.4 Registers read with function code FC03
Overview
Function code FC03 enables read access for the controller to one or more converter registers.
Functions
14.5Modbus TCP communication