17.9.4 3 AC 380 V … 415 V / 3 AC 440 V … 500 V, degree of protection IP55
Technical data
Table 17-19 Absolute power loss in W at operating point (90/100)
1)
Article number Rated power IEC NEC
6SL4113-...☐☐-..
F0
@ 400V, 50Hz @ 480V, 60Hz
Unltered Filtered Unltered Filtered
08 1.1kW 85.5 85.8 82.2 82.4
10 1.5kW 96.8 97.3 86.5 86.8
11 2.2kW 123 124 108 109
12 3kW 156 158 131 132
13 4kW 193 196 156 157
15 5.5kW 249 254 217 220
16 7.5kW 325 334 266 271
17 11kW 440 448 371 375
18 15kW 573 585 476 483
20 18.5kW 557 560 505 507
21 22kW 655 660 603 607
23 30kW 887 895 764 770
24 37kW 1103 1115 990 1000
26 45kW 1237 1242 1111 1115
27 55kW 1619 1627 1440 1446
1)
The operating point (90/100) means: relative motor stator frequency 90%, relative torque current 100%
Power loss was measured at a pulse frequency of 4kHz and with space-vector modulation.
17.9.5 Data regarding the power loss in partial load operation
Description
The energy eciency and power loss data of SINAMICS frequency converters are compliant with
the ecodesign standard IEC 61800-9-2 and the ecodesign regulation (EU) 2019/1781.
The standard IEC 61800-9-2 denes the ecodesign requirements for drive systems in the
low-voltage range, based on an electrically driven machine in frequency converter operation.
Data regarding the power loss in partial load operation are documented in the converter data
sheet. The data sheet is provided in the Siemens Product Congurator in the Internet.
SPC (
https://mall.industry.siemens.com/spice/cloudcm/dashboard)
Technical data
17.9Power loss
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB 817