1. Press the catch marked in the diagram to the right and slide the sheet-metal plate down again.
2. Tighten the two screws to a torque of 2Nm.
7.1.4.3 Connection overview, converter in degree of protection IP55
Requirement
Only copper cables with an insulation that is designed for an ambient temperature of 75 °C are
permissible.
IP55 converter
$POWFSUFS
#SBLJOHSFTJTUPS
9-
-
-
8
7
96
%$/
-
-
-
1&
1&
3
3
9%$1
3
Figure7-8 Connection overview up to frame size FSC
Connecting
7.1Line system, motor and braking resistor
SINAMICS G220 converter
160 Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB