EasyManua.ls Logo

Siemens SINAMICS G220 - Automatic Restart

Siemens SINAMICS G220
834 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
14.11.12 Automatic restart
Overview
When the automatic restart function is active, the converter acknowledges faults and
automatically starts the motor.
Requirement
WARNING
Unexpected motion as a result of an automatic hot restart
An activated automatic restart can initiate unexpected machine motion that may result in
death or sever injury.
Only activate the automatic restart function if this cannot result in any dangerous situation.
In the system or at the machine, clearly mark that the drive can automatically restart.
Description of function
p1210 activates the automatic restart function corresponding to the requirements of the
speci󹪝c application.
The automatic restart function includes 2 di󹪜erent subfunctions:
The converter acknowledges faults automatically.
After a fault or a power failure, the converter switches on the motor again automatically.
The converter interprets the following events as a power failure:
The converter signals fault F30003 (undervoltage in the DC link) after the line voltage of the
converter was brie󹪞y interrupted.
All power supplies of the converter were interrupted and all the energy storage devices in the
converter were discharged to such a level that the converter electronics failed.
For certain faults, p1206[0...9] suppresses the automatic restart.
The following diagram shows the principle of operation of the automatic restart function.
Functions
14.11Drive functions
SINAMICS G220 converter
610 Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB

Table of Contents

Related product manuals