The temperature monitoring of explosion-protected motors requires short-circuit protection
of the sensor cable depending on the sensor cable length:
• Sensor cable length ≤250m: Short-circuit detection by the OM-SMT
• Sensor cable length >250m: Additional short-circuit protective measures, e.g. separate
routing or special rails
The protective measures must be evaluated in a risk analysis.
4.14.12 Achievable EMC category and maximum motor cable length
Requirement
Reliable and disturbance-free converter operation is only ensured when it is installed in an EMC-
compliant way.
Description
The achievable EMC category is dependent on the motor cable length and the line system
conguration. The following conditions apply to the permissible application environment.
Application environment Achievable EMC category
C2 C4
4)
Converter with integrated
line lter
3)
Converter without in‐
tegrated line lter
Cable length Motor ≤ 150m shielded CY cable ≤ 200m shielded
≤ 300m unshielded
Braking resistor ≤ 10m shielded CY cable ≤ 10m shielded
Installation loca‐
tion
Residential environment No No
Light industry and com‐
merce
Yes No
Heavy industry Yes Yes
2)
Line supply Public Yes
1)
No
Non-public Yes Yes
2)
Permissible line system conguration TN or TT system with groun‐
ded neutral point
Any
1)
Corresponds to IEC61000-3-12, Table 4, for RSC ≥120. The compatibility level for harmonic voltage
distortions at the line connection point must be taken into consideration
2)
Complex, large-scale industrial applications and/or IT supply networks. An EMC plan must be drawn up.
3)
Operation with the default pulse frequency or with reduced pulse frequency
4)
An external line lter is required to comply with the requirements relating to CE certication.
Application planning
4.14EMC-compliant installation
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB 91