Table 14-32 Response of the converter to an invalid write request
Value Byte Description
Modbus Applica‐
tion Header
- 0 … 6 -
Protocol Data Unit 86h 7 Highest bit = 1 and function code
01h
04h
8 Error code
14.5.6 Registers write with function code FC16
Overview
Function code FC16 enables write access for the controller to multiple converter registers.
Function code FC16 is suitable in particular for writing the control parameters using registers
40150 et seq.
Requirement
The registers accessed by the controller must be consecutive with no gaps.
Description of function
The structure of the protocol data unit (PDU) in the case of write access using function code
FC16 is as follows:
Byte7: FCode 16
Byte8 and Byte9: Register
Byte10 and Byte11: Number of registers to which controller is writing
Byte 12: Number of bytes the controller is writing
Byte 13 and following bytes: Data the controller is writing
Functions
14.5Modbus TCP communication
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB 393