Requirement
The motor is being operated without an encoder.
The pulse technique for continuously estimating the rotor position of a synchronous
reluctance motor is not active.
Description of function
A 0 signal in r1751.0 indicates that at low speeds the closed-loop speed control is in the open-
loop controlled mode. In the open-loop controlled mode, the converter injects a current into the
motor.
Resonance damping is active in the open-loop controlled mode. p1740 denes the controller
gain for resonance damping.
Parameters
The following list contains the parameters of the "Resonance damping" function.
Number Name Unit
r0066 Output frequency [Hz]
p1740[0...n] Gain resonance damping for encoderless closed-loop control
r1751.0...22 Motor model status
14.10.5.7 Setting motor control for critical applications
Overview
For critical applications, for example, with high load inertia, the speed control can become
unstable.
Requirement
Critical applications arise in the following constellations:
• High load moment of inertia compared with the motor moment of inertia
• Gearbox play or coupling play between the motor and load machine
• Vibrating coupling between the motor and load machine
Functions
14.10Closed-loop drive control
SINAMICS G220 converter