14.10.5.4 Vdc_min controller (Vdc_min control)
Overview
The Vdc_min controller (kinetic buering) increases the drive availability because the kinetic
energy of the load accommodates brief power dips or failures.
Requirement
Requirements:
• The driven load has a suciently high inertia.
• The application allows braking of the motor during a power failure.
Description of function
When the power dips or fails, the DC link voltage in the converter decreases. The Vdc_min
controller intervenes starting from an adjustable threshold. With kinetic buering active, the
converter covers its power loss and the losses in the motor with the kinetic energy of the load.
The speed of the load decreases but the DC link voltage remains constant with the Vdc_min
controller active. After the line supply returns, the converter resumes normal operation.
The Vdc_min controller can typically accommodate power failures of up to 1 second.
1PXFSGBJMVSF
7ED@NJODPOUSPMMFSJTBDUJWF
4QFFE
%$MJOLWPMUBHF
4XJUDIPOMFWFM
4QFFEUISFTIPME
(FOFSBUJOHPQFSBUJPO
U
U
Figure14-118 Principal mode of operation of the Vdc_min controller
Parameters
The following list contains the parameters of the "Vdc_min controller (Vdc_min control)"
function for speed control.
Number Name Unit
r0056.0...15 Status word, closed-loop control
p0210 Device supply voltage [V]
Functions
14.10Closed-loop drive control
SINAMICS G220 converter
512 Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB