7.1.7.2 Overcurrent protection, 3AC200 ...240V
Description
Table 7-23 Standard fuses according to IEC standard, 3AC200 ...240V
Converter Standard fuse Minimal electrical cabi‐
net envelope dimen‐
sions for converters
with degree of protec‐
tion IP20
Rated power /
kW
Article number Article number Rated current / A ICC / kA @
240V
0.55 6SL4112-...05-..F0 3NA3801 6 100 0.192 m³ 6.78 ft³
0.75 6SL4112-...06-..F0 3NA3803 10 100 0.192 m³ 6.78 ft³
1.1 6SL4112-...08-..F0 3NA3803 10 100 0.192 m³ 6.78 ft³
1.5 6SL4112-...10-..F0 3NA3805 16 100 0.192 m³ 6.78 ft³
2.2 6SL4112-...11-..F0 3NA3805 16 100 0.192 m³ 6.78 ft³
3 6SL4112-...12-..F0 3NA3807 20 100 0.24m³ 8.48ft³
4 6SL4112-...13-..F0 3NA3812 32 100 0.24m³ 8.48ft³
5.5 6SL4112-...15-..F0 3NA3817 40 100 0.12m³ 4.24ft³
7.5 6SL4112-...16-..F0 3NA3820 50 100 0.12m³ 4.24ft³
11 6SL4112-...17-..F0 3NA3824 80 100 0.36m³ 12.71ft³
15 6SL4112-...18-..F0 3NA3830 100 100 0.36m³ 12.71ft³
18.5 6SL4112-...20-..F0 3NA3830 100 100 0.36m³ 12.71ft³
22 6SL4112-...21-..F0 3NA3832 125 100 0.384m³ 13.56ft³
30 6SL4112-...23-..F0 3NA3836 160 100 0.384m³ 13.56ft³
Table 7-24 Semiconductor fuses according to UL/CSA standard, 3AC200 ...240V
Converter Semiconductor fuses Minimal electrical cabi‐
net envelope dimen‐
sions for converters
with degree of protec‐
tion UL open type
Rated power /
kW
Article number Article number Rated current / A SCCR / kA @
240V
0.55 6SL4112-...05-..F0 3NE1813-0 16 100 0.192 m³ 6.78 ft³
0.75 6SL4112-...06-..F0 3NE1813-0 16 100 0.192 m³ 6.78 ft³
1.1 6SL4112-...08-..F0 3NE1813-0 16 100 0.192 m³ 6.78 ft³
1.5 6SL4112-...10-..F0 3NE1813-0 16 100 0.192 m³ 6.78 ft³
2.2 6SL4112-...11-..F0 3NE1813-0 16 100 0.192 m³ 6.78 ft³
3 6SL4112-...12-..F0 3NE1814-0 20 100 0.24m³ 8.48ft³
4 6SL4112-...13-..F0 3NE1815-0 25 100 0.24m³ 8.48ft³
5.5 6SL4112-...15-..F0 3NE1802-0 40 100 0.12m³ 4.24ft³
7.5 6SL4112-...16-..F0 3NE1817-0 50 100 0.12m³ 4.24ft³
11 6SL4112-...17-..F0 3NE1820-0 80 100 0.36m³ 12.71ft³
15 6SL4112-...18-..F0 3NE1021-0 100 100 0.36m³ 12.71ft³
18.5 6SL4112-..20-..F0 3NE1021-0 100 100 0.36m³ 12.71ft³
Connecting
7.1Line system, motor and braking resistor
SINAMICS G220 converter