IEC 61800-3 denes the categories for electromagnetic compatibility.
Table 4-3 Application environments and categories according to IEC 61800-3
Low-voltage net‐
work
Public supply network Non-public and industrial supply networks
Application envi‐
ronment
Residential Commercial/
light industry
Industry /
Large-scale
plants
Heavy industry
High-frequency in‐
terference
Category C1 Category C1 or
C2
Category C2 or
C3
Category C3 Category C4
1)
Voltage, current <1000V ≥1000V
or
≥400A
Line system cong‐
uration
TN, TT TN, TT, IT
Installation, com‐
missioning
No require‐
ment
By specialist personnel
1)
Precondition: Plant manufacturers and operating companies agree on plant-specic measures in an
appropriate EMC plan. If specied in the product documentation, the drive can also be operated on
ungrounded line supplies (IT line systems) in accordance with product standard IEC61800‑3
More information
To comply with product standards of plants and/or machines, when integrating the drive in
plants or machines, additional measures may be required. The additional measures are the
responsibility of the plant builder or machine OEM.
Disturbance-free operation of the drive is only guaranteed when specialist personnel carry
out the installation work in strict compliance with EMC regulations.
4.13.4 Limit values for current harmonics in the industrial supply
Description
IEC61800‑3 does not dene any current harmonic limits when converters are operated on
industrial line supplies. A system evaluation according to IEC61000‑3‑14 or
IEC61800‑3AnnexB.4 is recommended.
More information
We recommend using the "TIA Selection Tool" conguring software to calculate the current
harmonics of the converter.
More information about the "TIA Selection Tool" is available on the Internet:
TIA Selection Tool (
https://www.siemens.com/tia-selection-tool)
Application planning
4.13Electromagnetic compatibility (EMC)
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB 79