Figure7-3 Power connections up to frame size FSC and from frame size FSD1
7.1.2 Connection, converter in degree of protection IP20, 3 AC 200 ... 240 V
Description
Rigid as well as exible cables can be connected.
Table 7-1 Connection at the converter for the braking resistor (line voltage 3AC 200...240V, IP 20)
Converter
6SL4112-..□□-..F0
Connection at the converter for the braking resistor
-..□□-
Frame
size
Rated pow‐
er in kW
Conductor cross-
section in mm²
(AWG)
Tightening torque in
Nm (lbfin)
Stripped
length in
mm (in)
Connection type
05 ... 11 A 0.55 ... 2.2 1.5 … 4(15 …11) 0.4 … 0.5 (3.5 … 4.4) 7 (0.3) Screw terminal
12 ... 13 B 3 ... 4 1.5 … 6(15 …9) 0.5 … 0.6 (4.4 … 5.3) 12 (0.5) Screw terminal
15 ...16 C 5.5 … 7.5 2.5 … 16(13 …5) 1.2 … 1.5 (10.6 … 13.3) 10 (0.4) Screw terminal
17...20 D2 11...18.5 10 … 16 (7 … 5) 1.2 … 1.5 (10.6 … 13.3) 10 (0.4) Screw terminal
21 ...23 E 22…30 16 … 35 (5 … 2) 3.7 … 4.5 (32.7 … 39.8) 18 (0.7) Screw terminal
Connecting
7.1Line system, motor and braking resistor
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB 153