Table 7-2 Connection at the converter for the motor (line voltage 3AC 200...240V, IP 20)
Converter
6SL4112-..□□-..F0
Connection at the converter for the motor
-..□□-
Frame
size
Rated pow‐
er in kW
Conductor cross-
section in mm²
(AWG)
Tightening torque in
Nm (lbfin)
Stripped
length in
mm (in)
Connection type
05 ... 11 A 0.55 ... 2.2 1.5 … 4(15 …11) 0.4 … 0.5 (3.5 … 4.4) 7 (0.3) Screw terminal
12 ... 13 B 3 ... 4 4 … 6(11 …9) 0.5 … 0.6 (4.4 … 5.3) 12 (0.5) Screw terminal
15 ...16 C 5.5 … 7.5 6 … 16(9 …5) 1.2 … 2(5.3 …17.7) 12 (0.5) Screw terminal
17...20 D2 11...18.5 10 … 50(7… 1/0) 5 … 6(44.3 …53.1) 19 (0.7) Screw terminal
21 ...23 E 22…30 35 … 95(2… 3/0) 10 … 12(88.5 …106.2) 25 (1) Screw terminal
Table 7-3 Line supply cable connection (line voltage 3AC 200...240V, IP 20)
Converter
6SL4112-..□□-..F0
Line supply cable
-..□□- Frame
size
Rated power
in kW
Conductor cross-
section in mm²
(AWG)
Tightening torque in
Nm (lbfin)
Stripped
length in
mm (in)
Connection type
05 ... 11 A 0.55... 2.2 1.5 … 4(15 …11) 0.4 … 0.5 (3.5 … 4.4) 7 (0.3) Screw terminal
12 ... 13 B 3 ... 4 4 … 6(11 …9) 0.5 … 0.6 (4.4 … 5.3) 12 (0.5) Screw terminal
15 ...16 C 5.5 … 7.5 6 … 16(9 …5) 1.2 … 2(5.3 …17.7) 10 (0.4) Screw terminal
17...20 D2 11...18.5 10 … 50(7… 1/0) 5 … 6(44.3 …53.1) 19 (0.7) Screw terminal
21 ...23 E 22…30 35 … 95(2… 3/0) 10 … 12(88.5 …106.2) 25 (1) Screw terminal
Table 7-4 Protective conductor in terminal X1 connection (line voltage 3AC 200...240V, IP 20)
Converter
6SL4112-..□□-..F0
Protective conductor in terminal X1
-..□□- Frame
size
Rated power
in kW
Conductor cross-
section in mm²
(AWG)
Tightening torque in
Nm (lbfin)
Connection type
05 ... 11 A 0.55... 2.2 1.5 … 4(15 …11) 2 … 3(17.7 …26.6) M4, screw terminal, outside
12 ... 13 B 3 ... 4 1.5 … 6(15 …9) 2 … 3(17.7 …26.6) M4, screw terminal, outside
15 ...16 C 5.5 … 7.5 1.5 … 16(15 …5) 2 … 3(17.7 …26.6) M4, screw terminal, outside
17...20 D2 11...18.5 1.5 … 50(15… 1/0) 4 … 5(35.4 …44.3) M5, screw terminal, outside
21 ...23 E 22…30 2.5 … 95(13… 3/0) 4 … 5(35.4 …44.3) M5, screw terminal, outside
Connecting
7.1Line system, motor and braking resistor
SINAMICS G220 converter
154 Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB