Table 7-26 Semiconductor fuses according to UL/CSA standard, 3 AC 380 V … 415 V / 3 AC 440 V … 500 V
Converter Semiconductor fuses Minimal electrical cabi‐
net envelope dimen‐
sions for converters
with degree of protec‐
tion UL open type
Rated power /
kW
Article number Article number Rated current / A SCCR / kA @
240V
0.55 6SL4113-...05-..F0 3NE1813-0 16 100 0.192m³ 6.78ft³
0.75 6SL4113-...06-..F0 3NE1813-0 16 100 0.192m³ 6.78ft³
1.1 6SL4113-...08-..F0 3NE1813-0 16 100 0.192m³ 6.78ft³
1.5 6SL4113-...10-..F0 3NE1813-0 16 100 0.192m³ 6.78ft³
2.2 6SL4113-...11-..F0 3NE1813-0 16 100 0.192m³ 6.78ft³
3 6SL4113-...12-..F0 3NE1813-0 16 100 0.192m³ 6.78ft³
4 6SL4113-...13-..F0 3NE1813-0 16 100 0.192m³ 6.78ft³
5.5 6SL4113-...15-..F0 3NE1814-0 20 100 0.24m³ 8.48ft³
7.5 6SL4113-...16-..F0 3NE1815-0 25 100 0.24m³ 8.48ft³
11 6SL4113-...17-..F0 3NE1802-0 40 100 0.12m³ 4.24ft³
15 6SL4113-...18-..F0 3NE1817-0 50 100 0.12m³ 4.24ft³
18.5 6SL4113-...20-..F0 3NE1818-0 63 100 0.288m³ 10.71ft³
22 6SL4113-...21-..F0 3NE1820-0 80 100 0.288m³ 10.71ft³
30 6SL4113-...23-..F0 3NE1021-0 100 100 0.36m³ 12.71ft³
37 6SL4113-...24-..F0 3NE1021-0 100 100 0.36m³ 12.71ft³
45 6SL4113-...26-..F0 3NE1022-0 125 100 0.384m³ 13.56ft³
55 6SL4113-...27-..F0 3NE1224-0 160 100 0.384m³ 13.56ft³
More information
You can nd more information about overcurrent protective devices on the Internet:
Protective devices for SINAMICS G220 (
https://support.industry.siemens.com/cs/ww/en/view/
109823568)
7.1.7.4 Residual current device (RCD)
Overview
Residual current devices are required in addition to overcurrent protection devices for certain
network characteristics.
The residual current device must not be triggered by leakage currents caused by operation.
Connecting
7.1Line system, motor and braking resistor
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB 173