6.1.4 Minimum clearances, converter in degree of protection IP20
Dimension drawing
.JOJNVN
DMFBSBODFBUUPQ
.JOJNVN
DMFBSBODFBU
CPUUPN
Figure6-4 IP20 minimum clearances
Table 6-2 Minimum clearances
Unit FSA FSB FSC FSD1 FSD2 FSE
Minimum venti‐
lation clearance
above
mm 85 85 85 90 90 90
Minimum venti‐
lation clearance
below
mm 85 108 149 160 160 193
Minimum venti‐
lation clearance
below with ex‐
tended shielding
plate
mm 147 --- --- --- --- ---
Recommended
minimum clear‐
ance at the front
mm 10 10 10 10 10 10
Mounting
6.1Converter
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB 133