14.12.9.6 Transferring the F-DI status via PROFIsafe
Overview
The con󹪝guration of the transfer of the F-DI status de󹪝nes the input mode of an F-DI, and
activates the transfer of an F-DI state to the F-control.
Requirement
A PROFIsafe telegram with transfer of the F-DI status is set.
The F-DI to be transferred is fully con󹪝gured:
Discrepancy time
Input 󹪝lter
Self-test
Description of function
c10050 selects the F-DI whose status the converter transfers to the F-control via PROFIsafe.
Parameters
The following list contains the parameters of the function "Transfer F-DI status via PROFIsafe".
Number Name Unit
c10050[0...2] SI status F-DI via PROFIsafe
14.12.9.7 Control via PROFIsafe and EMERGENCY STOP via terminals
Overview
After con󹪝guration, PROFIsafe communication and a stop function for EMERGENCY STOP via
terminals are de󹪝ned.
Description of function
Using PROFIsafe, Safety Integrated Functions can be selected and deselected, and safety faults
can be safely acknowledged.
EMERGENCY STOP is permanently assigned to F-DI 0. The following functions can be selected:
Safe Torque O󹪜 (STO)
Safe Stop 1 (SS1)
Safe Stop 1 with external stop (SS1E)
Functions
14.12Safety Integrated
SINAMICS G220 converter
692 Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB