WARNING
Electric shock as a result of a residual charge in power components
After the power supply has been switched o, it takes up to 5 min. until the capacitors in the
converter have discharged so that the residual charge is at a non-hazardous level. Touching live
components can result in death or severe injury.
• Check that there is absolutely no voltage between any of the power connections, or
between them and the protective conductor connection.
Procedure
Figure7-11 Removing the screw for functional grounding (example: Converter with frame size FSC)
Proceed as follows to open the ground connection of the integrated line lter:
1. Open the protective ap at the converter housing, e.g. using a slotted screwdriver.
2. Release the screw for the ground connection and remove it.
7.1.6 Opening the ground connection of the integrated line lter, degree of
protection IP55
Overview
When connecting the converter with integrated line lter to an IT line system, the ground
connection of the integrated line lter must be open.
Connecting
7.1Line system, motor and braking resistor
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB 167