4.14.9 Shielded cables and ferrites, converter in degree of protection IP55
Description
7TVQQMZ
-JOFMUFS
#SBLJOHSFTJTUPS
$POWFSUFS
.PUPS&ODPEFS5FNQFSBUVSF
TFOTPS
'JFMECVTDBCMF
$BCMFTGPSEJHJUBMJOQVUT
BOEPVUQVUT
$BCMFTGPSBOBMPHJOQVUT
BOEBOBMPHPVUQVUT
$BCMFUPUIFFEHFEFWJDF
_
_
1)
Optional external line lter
2)
We recommend the following two measures to ensure compliance with EMC standards when using
an external braking resistor on the converter with the frame size FSD1, FSD2 and FSE:
1. Selection of a suitable EMC toroidal core, e.g. Magnetec, type: M-612-02, or equivalent
2. Selection of suitable and proper securing of the EMC toroidal core
Securing the EMC toroidal core is not shown in the gure above.
The user is responsible for the selection and attachment of the EMC toroidal core according to 1 and
2.
Figure4-9 EMC-compliant cable shielding ferrite cores
With the exception of the line supply cable, all cables must be shielded to comply with EMC
regulations.
Application planning
4.14EMC-compliant installation
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB 89