14.4.6.16 NAMUR message word
Overview
The NAMUR message word signals the converter status to the higher-level control system.
Description of function
NAMUR message word (MELD_NAMUR)
Converter → Control
Bit Meaning
00 1 = Converter control unit fault
01 1 = Line supply fault: Phase failure or inadmissible voltage
02 1 = DC link overvoltage
03 1 = Power unit fault, e.g. overcurrent or overtemperature
04 1 = Converter overtemperature
05 1 = Ground fault/inter-phase short-circuit in the motor cable or motor
06 1 = Motor overload
07 1 = Communication error with the higher-level control system
08 1 = Error in a safety monitoring channel
09 Reserved
10 1 = Converter-internal communication error
11 1 = Line system fault
12 …
14
Reserved
15 1 = Other fault
Parameters
The following list contains the parameters of the "Control and status word 3" function.
Number Name Unit
r3113.0...15 NAMUR message bit bar
14.4.6.17 Control and status word encoder
Overview
The encoder control word (G1_STW and G2_STW) and the encoder status word (G1_ZSW and
G2_ZSW) allow the higher-level control to directly access the functions and status of the encoder.
Direct access to the encoder is necessary, if the higher-level control performs the closed-loop
position control for the drive.
Functions
14.4PROFINET communication
SINAMICS G220 converter
358 Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB