14.5 Modbus TCP communication
14.5.1 Modbus TCP 󹪝eldbus
Overview
Modbus TCP is a 󹪝eldbus standard used by the converter to communicate with a higher-level
control system.
Requirement
Converter with Ethernet interface X150
Following selection of Modbus TCP in the commissioning tool, the power supply must be
switched o󹪜 and then switched on again or a hardware reset must be performed via p0972.
Description of function
The Modbus protocol, which is based on a controller-device architecture, transfers data as
TCP/IP packets.
The converter supports connection to a maximum of three controllers.
TCP port 502 is reserved for Modbus TCP.
The higher-level control system accesses converter process data and parameters via registers.
Process data: Registers 40100 - 40119
Drive data: Registers 40300 - 40522
Parameters via DS47: Registers 40601 - 40722
Modbus TCP always provides a basic Ethernet functionality:
Commissioning access
DCP, for example for setting the IP address
SNMP for identi󹪝cation
14.5.2 Register
Overview
The Modbus protocol contains register and bit numbers for addressing memory. The registers
are assigned in converter control words, condition words and parameters of the converter.
Functions
14.5Modbus TCP communication
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB 385