The reset has been completed if the "RDY" and "COM" LEDs on the converter light up green.
More information
For a full reset of the converter, proceed as described in section "Full reset of all device settings
(Page777)".
10.5.5.7 Restore Safety Integrated to factory settings
Overview
It is not always necessary to reset all of the converter settings. A separate reset function exists
for Safety Integrated settings, which exclusively restores Safety Integrated settings to factory
settings.
Requirement
Requirements:
Before carrying out a reset, save the drive data in a backup 󹪝le so that you can access the
settings again.
Function rights required for active user management (UMAC):
Edit device con󹪝guration or drive applications
Edit Safety Integrated application
Procedure
1. Call the "Backup and restore" menu.
2. Click on the "Reset Safety Integrated" button.
3. Acknowledge the con󹪝rmation prompt.
4. Wait: the converter resets its Safety Integrated settings.
5. Wait: the converter restarts.
6. The converter is ready for operation and the "RDY" and "COM" LEDs light up green.
Result
The Safety Integrated settings for the converter have been reset.
Commissioning (web server)
10.5Functions and menus
SINAMICS G220 converter
262 Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB