14.12.9.12 F-DO con󹪝guration
Overview
The F-DO con󹪝guration interconnects up to 6 signals of the Safety Integrated Functions with the
failsafe digital output (F-DO).
Requirement
To output the status of a Safety Integrated Function over the F-DO, the Safety Integrated
Function must be enabled.
Description of function
The F-DO con󹪝guration interconnects multiple status signals with the failsafe output (F-DO).
ANDing the following signals produces the status of the F-DO:
Status of the Safety Integrated Functions
Safe State
The "Safe State" signal is the ORing of the statuses of multiple Safety Integrated Functions.
Parameters
The following list contains the parameters of the "Safe State and F-DO con󹪝guration" function.
Number Name Unit
p9603.0...1 SI control
r9722.0...15 SI status signals
r10038 SI Safe State status
p10039.0...10 SI Safe State signal selection
c10042[0...5] SI F-DO 0 signals of the AND logic operation
14.12.9.13 Self-test of the fail-safe digital output
Overview
The self-test detects whether the fail-safe digital output can be switched into the safe state.
F-DO0+ switches to the Low state
F-DO0- switches to the High state
The converter responds with a fault if there is an unexpected feedback signal during the
self-test.
Functions
14.12Safety Integrated
SINAMICS G220 converter
702 Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB