Procedure
1. Select a drive in the project tree.
2. Click on icon
(Load to device) in the toolbar.
– If you have already established an online connection, then the "Load preview" dialog
opens.
This dialog displays alarms and proposes actions necessary for loading.
– If you have still not established an online connection, then the "Extended loading" dialog
opens.
Using this dialog, establish an online connection to the required drive.
3. Check the messages in the "Load preview" dialog.
The "Save parameterization retentively" action is enabled by default.
4. Click "Load".
The project data is downloaded into the drive.
11.2.5 Saving changes in the project
Overview
Project data that are not saved are lost when closing the project. The entire project must be saved
in order for the settings to take eect permanently.
Requirement
• Project protection is active
The following function rights for editing drive data are activated for your user account:
– "Open and edit the project"
– "Edit hardware conguration"
– "Edit drive applications"
– "Edit drive Safety Integrated application"
– "Manage users and roles"
Details on this topic are provided in the Conguration Manual SINAMICS Industrial Security
(
https://support.industry.siemens.com/cs/ww/en/view/109810578) in Chapter "Security
settings in Startdrive".
Procedure
In the toolbar, click on the icon .
OR
Select the "Project>Save" or "Project>Save as" menu.
Commissioning (Startdrive)
11.2Basics
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB 279