4.14.6 Electrical isolation between the process control level and eld level
Description
Field level
Electrical isolation
required
Process control level
Gateway
Ethernet
Figure4-7 Electrical isolation between the process control level and eld level
If the control level and eld level of the eldbus are connected through a gateway, then
optical or electrical isolation is required in the gateway, for example using a Simatic Scalance
X101-1 media converter.
Within the eld level, electrical isolation between individual segments of the eldbus is
possible when required.
Application planning
4.14EMC-compliant installation
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB 85