p1212 Automatic restart wait time, acknowledgment and start
attempt
[s]
p1213[0...1] Automatic restart monitoring time [s]
14.11.13 Flying restart - switching on while motor is running
Overview
If you switch on the motor while it is still rotating, a fault due to overcurrent (F30001 or F07801)
is highly likely unless the "Flying restart" function is used.
Examples of applications involving an unintentionally rotating motor directly before
switching on:
The motor is rotating after a brief power interruption.
A 󹪞ow of air is turning a fan impeller.
A load with a high moment of inertia is driving the motor.
Requirement
Permissible drives:
Single drive
Mechanically coupled group drive
Group drive without mechanical coupling is not permissible.
Description of function
The converter determines the motor speed continuously during the "Flying restart" function.
Following the ON command, the converter synchronizes its output frequency with the
motor speed and magnetizes the motor. The converter sets its output frequency to 0Hz
for magnetization at motor speeds <10% of the rated speed. If it is not possible to start in
this range, p1270.2 activates a supportive search technique.
5IFDPOWFSUFSNBHOFUJ[FTUIF
NPUPS
0/0''
4QFFE
U
Figure14-197 Principle of operation of the "Flying restart" function
Parameters
The following list contains the parameters of the "Flying restart" function.
Functions
14.11Drive functions
SINAMICS G220 converter
612 Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB

Table of Contents

Related product manuals