Sum of the magnetizing time and the time for the ying restart of the motor
① A fault activates the automatic restart function.
② 1st attempt of the automatic restart starts.
The converter decrements the counter of the automatic restart attempts.
Fault F07320 is output if the counter value of the restart attempts < 0
③ 1st attempt of the automatic restart fails as a result of a new fault.
④ 2nd attempt of the automatic restart starts.
⑤ 2nd attempt of the automatic restart is successful.
If no fault has occurred one second after the ying restart of the motor, then the automatic restart
attempt was successful.
⑥ The automatic restart must be successful within p1213[0]. If not, fault F07320 is output
⑦ After p1213[1], the converter resets the automatic restart attempts to p1211.
Figure14-196 Time response of the automatic restart
Parameters
The following list contains the parameters of the "Automatic restart" function.
Number Name Unit
r0056.0...15 Status word, closed-loop control
p1206[0...9] Automatic restart faults not active
p1210 Automatic restart mode
p1211 Automatic restart start attempts
Functions
14.11Drive functions
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB 611