Converter
6SL4113-..□□-..F0
Protective conductor connection in terminal X1
-..□□- Frame
size
Rated power in
kW
Conductor cross-sec‐
tion in mm² (AWG)
Tightening torque in
Nm (lbfin)
Connection type
23...24 D2 30...37 2.5 … 50 (13...1/0) 5 … 6(44.2 …53.1) M8, screw terminal, outside
26 ...27 E 45...55 4 … 95 (11...3/0) 8 … 9(70.8 …79.7) M8, screw terminal, outside
Table 7-22 Protective conductor connection at terminal X2 (line voltage 3AC 380...415 / 3AC440...500V, IP 55)
Converter
6SL4113-..□□-..F0
Protective conductor in terminal X2
-..□□- Frame
size
Rated power in
kW
Conductor cross-sec‐
tion in mm² (AWG)
Tightening torque in
Nm (lbfin)
Connection type
08…16 B 1.1 … 7.5 1.5 … 6(15 …9) 2 … 3(17.7 …26.6) M4, screw terminal, inside
17 ...18 C 11 ... 15 1.5 … 16(15 …5) 2 … 3(17.7 …26.6) M4, screw terminal, inside
20...21 D1 18.5...22 2.5 … 50 (13...1/0) 5 … 6(44.2 …53.1) M6, stud terminal, inside
23...24 D2 30...37 2.5 … 50 (13...1/0) 5 … 6(44.2 …53.1) M6, stud terminal, inside
26 ...27 E 45...55 4 … 95 (11...3/0) 8 … 9(70.8 …79.7) M8, stud terminal, inside
7.1.5 Opening the ground connection of the integrated line 󹪝lter, degree of
protection IP20
Overview
When connecting the converter with integrated line 󹪝lter to an IT line system, the ground
connection of the integrated line 󹪝lter must be open.
Requirement
Switch o󹪜 the converter power supply.
CAUTION
Damage to the converter when connected to an IT line system
The converter will be damaged if it is operated with integrated line 󹪝lter on an IT line system.
Open the ground connection of the integrated line 󹪝lter.
Connecting
7.1Line system, motor and braking resistor
SINAMICS G220 converter
166 Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB