4.4 Requirements for the protective conductor, converter in degree
of protection IP20
Overview
A high leakage current ows through the protective conductor in converter operation. The
protective conductor of the converter must not be interrupted to ensure safe touch protection
in converter operation.
Requirement
WARNING
Electric shock due to interrupted protective conductor
The drive components conduct a leakage current via the protective conductor. Touching
conductive parts when the protective conductor is interrupted can result in death or serious
injury.
• Comply with the requirements for the protective conductor.
Description
The leakage current via the protective conductor of the converter can exceed the following
values:
• 3.5mA DC current
• 10mA AC current
This results in minimum requirements for the protective conductor.
Application planning
4.4Requirements for the protective conductor, converter in degree of protection IP20
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB 65