Table 14-41 Read parameter response: Write parameter value of p1121
Value Byte Description
Modbus Appli‐
cation Header
- 0 … 6 -
Protocol Data
Unit
03h 7 Function code
0258h 8, 9 Register (40601)
0007h 10, 11 Number of registers to be read (40601 … 40607)
Table 14-42 Response of the converter to a valid write request
Value Byte Description
Modbus Appli‐
cation Header
- 0 … 6 -
Protocol Data
Unit
03h 7 Function code
0Eh 8 Number of bytes (0Eh: 14 bytes ≙ 7 registers)
0002h 9, 10 40601: DS47 Control= 2 (the request was executed)
2F04h 11, 12 40602: Function code 2F h (47), response length 4 bytes
8002h 13, 14 40603: Request reference mirrored = 80 h, response identier = 2
(write parameter)
0101h 15, 16 40604: Drive object = 1, number of parameters = 1
Table 14-43 Response if write request has still not been completed
Value Byte Description
Modbus Appli‐
cation Header
- 0 … 6 -
Protocol Data
Unit
03h 7 Function code
0Eh 8 Number of bytes (0Eh: 14 bytes ≙ 7 registers)
0001h 9, 10 40601: Check value 1 = request being processed
2F00h 11, 12 40602: Function code 2F h (47), response length 0 (error)
0004h 13, 14 40603: Response has still not been issued
14.5.8 Response to an invalid write or read access attempt
Overview
The converter signals an erroneous read or write access attempt to the controller with an error
code.
Functions
14.5Modbus TCP communication
SINAMICS G220 converter
398 Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB