Parameters
The following list contains the parameters of the "Diagnostics with PROFINET" function.
Number Name Unit
r0947[0...63] Fault number
r2122[0...63] Alarm code
r3120[0...63] Component fault
r3121[0...63] Component alarm
14.4.9 Identication & Maintenance (I&M) data
Overview
I&M data are identication and maintenance data that are stored in a device. The higher-level
controller has access to the I&M data of all devices on the eldbus.
Using the I&M data, the plant operator can identify and label devices and dene maintenance
measures.
The converter supports the identication and maintenance (I&M) data listed in the table.
Description of function
Table 14-12 I&M data
I&M data Format Explanation Example for the
content
I&M0 u8[64] PROFIBUS
u8[54] PROFINET
Converter-specic data, read only See below
I&M1 Visible String [32] Plant/system identier "ak12-ne.bo2=fu1"
Visible String [22] Location code "sc2+or45"
I&M2 Visible String [16] Date "2013-01-21 16:15"
I&M3 Visible String [54] Any comment or remark -
I&M4 Octet String[54] Check signature to track changes for Safe‐
ty Integrated.
Values of r9781[0]
and r9782[0]
When requested, the converter transfers its I&M data to a higher-level control or to a PC/PG
with installed STEP7 or TIAPortal.
Table 14-13 I&MO
Designation Format Example for the content
MANUFACTURER_ID u16 42dhex (=Siemens)
ORDER_ID Visible String [20] "6SL3246-0BA22-1FA0"
SERIAL_NUMBER Visible String [16] "T-R32015957"
HARDWARE_REVISION u16 0001hex
Functions
14.4PROFINET communication
SINAMICS G220 converter