14.11.16.16 Setting motor overload protection according to UL 61800-5-1
Overview
If you operate the motor with a temperature sensor, the converter complies with motor overload
protection according to UL61800‑5‑1 Ed.2.
You must make some additional settings if you operate the motor without a temperature
sensor.
Requirement
Requirements:
You have completed quick setup with the correct motor data.
You are operating the motor without a temperature sensor.
Procedure
To activate motor overload protection according to UL 61800‑5‑1 Ed. 2, proceed as follows:
1. Set p5375.0=1
2. Set p5375.1=1
Functions
14.11Drive functions
SINAMICS G220 converter
638 Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB