- 8010 -
1
Signals and monitoring functions
Speed signals (part 1)
© Siemens AG
2 3 4 5 6 7 8
V6.02.00
<1>
r2197
r2197.6
1 = |n_act| > n_max
r2199
r2199.0
1 = |n_act| < speed threshold 3
r2199
r2199.1
1 = f or n comparison value
reached or exceeded
r2197
r2197.1
1 = |n_act| <= speed
threshold 2 p2155
r2197
r2197.2
1 = |n_act| > speed
threshold 2 p2155
n
0
n
Speed actual value
filter time constant
0 ... 1000000 [ms]
p2153 [D] (0)
[8011.1], [8013.1],
[8015.1], [8022.1],
[8023.1]
Hysteresis speed n_act > n_max
0.00 ... 60000.00 [rpm]
p2162 [D] (0.00)
0
1
Speed threshold 3
0.00 ... 210000.00 [rpm]
p2161 [D] (5.00)
Hysteresis speed 3
0.00 ... 300.00 [rpm]
p2150 [D] (2.00)
0
1
Speed threshold 1
0.00 ... 210000.00 [rpm]
p2141 [D] (5.00)
Hysteresis speed 1
0.00 ... 300.00 [rpm]
p2142 [D] (2.00)
0
1
Speed threshold 2
0.00 ... 210000.00 [rpm]
p2155 [D] (900.00)
Hysteresis speed 2
0.00 ... 300.00 [rpm]
p2140 [D] (90.00)
0
1
Speed threshold 2
0.00 ... 210000.00 [rpm]
p2155 [D] (900.00)
Hysteresis speed 2
0.00 ... 300.00 [rpm]
p2140 [D] (90.00)
<1>
<1>
<1>
<1>
T 0
0
1
T 0
0
1
1
Calculated.
0
1
T 0
1 = n_act > p2155 own hysteresis
p2149.3 [D]
On-delay comparison value reached
0.0 ... 10000.0 [ms]
p2156 [D] (0.0)
F07901
"Motor overspeed"
r1084
Positive speed limit effective [rpm]
r1087
Negative speed limit effective [rpm]
r2169
Actual speed smoothed signals [rpm]
r0063[0]
Speed actual value Unsmoothed [rpm]
[2534.4]
[2534.4]
[2534.4]
[2537.4]
[2537.4]
Figure14-209 8010 – Speed messages (part1)
Functions
14.11Drive functions
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB 639