Signals and monitoring functions
Speed signals (part 2)
© Siemens AG
2 3 4 5 6 7 8
V6.02.00
<2>
r2169
Actual speed smoothed
signals [rpm]
c2151 [C]
(1170)
Speed setpoint for messages/signals
[8010.3]
[3080.8]
–
+
Hysteresis speed 3
0.00 ... 300.00 [rpm]
p2150 [D] (2.00)
Speed threshold 4
0.00 ... 210000.00 [rpm]
p2163 [D] (90.00)
Hysteresis speed 4
0.00 ... 200.00 [rpm]
p2164 [D] (2.00)
Speed threshold 3
0.00 ... 210000.00 [rpm]
p2161 [D] (5.00)
Hysteresis speed 3
0.00 ... 300.00 [rpm]
p2150 [D] (2.00)
Hysteresis speed 3
0.00 ... 300.00 [rpm]
p2150 [D] (2.00)
Off-delay n_act = n_set
0.0 ... 10000.0 [ms]
p2166 [D] (200.0)
1 = Enable alarm A07903
p2149.0 [D]
r2197
r2197.7
1 = Speed setpoint - actual value deviation in tolerance t_off
r2198
r2198.4
1 = |n_set| < p2161
r2198
r2198.5
1 = n_set > 0
r2199
r2199.4
1 = Speed setpoint - actual value deviation in tolerance t_on
r2199
r2199.5
1 = Ramp-up/ramp-down completed
r2197
r2197.3
1 = n_act >= 0
0
1
[2534.4]
0
1
0
1
0
0
1
1
r1407.2
1 = Torque control active
T 0
0 T
Switch-on delay n_act = n_set
0.0 ... 10000.0 [ms]
p2167 [D] (200.0)
SET
(Q=1)
RESET
(Q=0)
Q
Q
1 = RESET
1
0
1
[2536.4]
[2536.4]
[2534.4]
<2>
[2537.4]
[2537.4]
Priority
1 RESET
2 SET
Evaluation only for:
Pulse enable and operating enable (r0899.2)
or OFF1
or OFF3
or rotating measurements.
A07903 "Motor speed deviation"
A07903 is only signaled for
p2149.0 = 1 and r2197.7 = 0.
Calculated.
<1>
<1>
<1>
<1>
<1>
<1>
c2154 [C]
(0.00)
Speed setpoint 2 for
messages [rpm]
+
[2522.7]
c2148 [C]
(0)
Ramp-function generator active
0
Figure14-210 8011 – Speed messages (part2)
Functions
14.11Drive functions
SINAMICS G220 converter
640 Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB